Applicable to all Oil & Gas Operators GUIDELINES FOR THE ESTABLISHMENT AND OPERATIONS OF GAS STORAGE AND UTILISATION FACILITIES IN NIGERIA Code: DPR Guide 0020 - 2020 Revision Date: 1st September 2020 This is a property of the Department of Petroleum Resources. All rights reserved 12 3.3.2 Separation distance for Downloading Facilities Each individual cylinder used for the storage or dispensing natural gas shall be located with respect to the nearest building or compressor equipment or other sources of ignition in accordance with table 3.2. Table 3.2: Isolation Distances from Building and Boundaries to as Storage Unit Total capacity of Gas storage (Cubic FT) Minimum distance (metres) Minimum on-site distance between Gas storage units and a 4hr. FRR concrete or Masonry wall (metres) Up to 1,100 (5MT) 5 2.0 1,100 to 2,450 (5MT-70 MT) 7.5 2.0 Note: a. A blast wall or fire clearance zone of a minimum 3 metres shall be maintained around the perimeter fence of any CNG storage facility. b. Firewall shall be installed to adjoining residential or public buildings 3.3.3 LPG Separation Distances The separation distance for LPG tanks within a Gas Storage and Utilization facility are depicted in Table 3.3 while the requirements for underground installations are depicted in Table 3.4.