Afrindustria/ Gas Gap Monitor

Library / GUIDE FOR THE ESTABLISHMENT AND OPERATIONS OF DOWNSTREAM GAS FACILITIES IN NIGERIA (LPG, CNG, LNG) ISSUED BY

GUIDE FOR THE ESTABLISHMENT AND OPERATIONS OF DOWNSTREAM GAS FACILITIES IN NIGERIA (LPG, CNG, LNG) ISSUED BY

Page 111 of 194

Open the PDF at page 111

 
 
 
 
Applicable to all Oil & Gas Operators  
GUIDELINES FOR THE ESTABLISHMENT AND OPERATIONS OF GAS 
STORAGE AND UTILISATION FACILITIES IN NIGERIA 
Code: DPR Guide 0020 - 2020 
 
Revision Date: 1st September 2020 
 
 
 
This is a property of the Department of Petroleum Resources. All rights reserved  
 
20 
vapour barrier; shall be water-free and shall resist dislodgment by fire hose 
systems. The space between the inner container and the outer container shall 
contain insulation that is compatible with LNG and is non-combustible. 
xi. Storage vessels shall be spaced and located in accordance with the provisions of 
this document. The layout shall consider the effects of a release of cryogenic liquid 
such that any release can rapidly evaporate and have minimum effect on the 
storage tank supporting structure to ensure that the storage tank remains 
adequately supported. 
xii. Ground features such as open drains, manholes, gullies and cellar hatches, within 
the separation distances should be sealed or trapped to prevent the passage of 
LNG vapour. 
3.4.5.1 LNG Boil-Off Gas Handling  
i. Boil-off and flash gas shall be set to discharge into a closed system or into the 
atmosphere to safe location.  
ii. Boil off venting systems shall be designed not to inspirate air during normal 
operations. 
3.5 
Facility Connecting Pipework and Valves 
Piping, Valves and fittings are to be fabricated, installed, and tested in line with 
international standard such as ASME Process Piping Code or any other applicable codes 
recognised by DPR.  Any exterior piping shall be buried or installed above ground shall be 
supported and protected against mechanical damage. Additionally, the following shall, at 
a minimum, apply: 
i. Pipes and pipework components (including weld/braze compounds) shall be of a 
material that is resistant to corrosion.