24 
3.9 
Protection against Static Electricity: 
The installation should have electrical continuity, be effectively connected to earth and 
bonded to comply with the requirements of the Institute of Petroleum's Model Code of 
Safe Practice, Part 1, Electrical and BS 7671:2001 or equivalent international standard. 
1. All piping, tanks, valves and discharge & dispensing equipment must be bonded 
continuously so that all non-current carrying metal parts have the same potential to 
ground that can potentially result in a catastrophic fire or explosion.  
2. All dispensing equipment including pumps, hoses and nozzles must be properly rated 
for the intended usage. 
3. Adequate explosion-proof lighting shall be provided to illuminate the working and 
the storage areas of the plant.  
 
3.10 Fire Protection 
The fire protection system of facility shall be required and designed to prevent or reduce 
the likelihood of a fire or explosion, to minimize its intensity should such an event occur 
and ensure timely emergency response and escape of all persons in the facility. The fire 
protection measures shall cater and ensure that adequate controls are  put in place, 
including special, technical and organizational measures taken for all work process, 
including receipt, storage and other activities  in connection with the Facility to  prevent 
fire/explosion; deal with the incident should such an event occur; and ensure emergency 
response and escape of all persons in the facility.  Additionally, the Gas Storage and 
Utilisation Facility shall, at the minimum, provide the following firefighting and emergency 
facilities: 
i. 
Clean Water Reservoir of minimum size 15 cubic metres.  
ii. 
Functional firefighting gadgets must be kept handy and at alert.