GUIDELINES FOR THE ESTABLISHMENT AND OPERATIONS OF CNG 
COMPRESSION FACILITIES IN NIGERIA 
Code: DPR Guide 0029 - 2020 
 
Revision  Date: 1st September 2020 
 
 
 
This is a property of the Department of Petroleum Resources. All rights reserved  
 
11 
vi. 
The siting of other activities which the facility may perform (e.g. parking areas, car 
wash facilities) shall not adverse safety and main vehicle flows on and off the site 
through the facility.  
vii. 
Electrical connections shall be made in accordance with the manufacturer's 
instructions and shall maintain the integrity of the explosion protection. 
viii. 
The minimum distances stated in section 3.3 must be complied with. 
 
3.3 
Separation Distances  
The minimum distance for the establishment of Additional Requirements for CNG 
Compression Facility.  
3.3.1 
Separation distance for Compression Facilities  
The distances given in table below indicate the minimum approved horizontal distances 
between the nearest point on the storage tank and a specified feature, e.g. an adjacent 
storage tank, building or boundary and the dispensers.  
Table 3.1 Isolation distances from building and boundaries to gas storage unit(s) 
Total capacity of Onsite Gas 
storage (Cubic FT) 
Minimum distance 
(metres) 
Minimum on-site distance between Gas 
storage units and a 4hr. FRR concrete or 
Masonry wall (metres) 
Up to 1,100 (5MT) 
5 
2.0 
1,100 to 2,450 (5MT-70 MT) 
7.5 
2.0 
Note: 
a. Each individual cylinder used for the storage or dispensing natural gas shall be 
located with respect to the nearest building or compressor equipment or other 
sources of ignition in accordance with table 3.1. 
b. A blast wall or fire clearance zone of a minimum 3 metres shall be maintained 
around the perimeter fence of any CNG storage facility.