GUIDELINES FOR THE ESTABLISHMENT AND OPERATIONS OF CNG 
COMPRESSION FACILITIES IN NIGERIA 
Code: DPR Guide 0029 - 2020 
 
Revision  Date: 1st September 2020 
 
 
 
This is a property of the Department of Petroleum Resources. All rights reserved  
 
13 
vii. 
Storage systems and vessels shall be fitted with over pressure protection devices 
to release excess pressure under normal operating conditions and in emergency 
situations.   
viii. 
Manually operated valves shall also be fitted to release pressure during 
maintenance. 
Note: All propane storage and handling facilities shall comply with Propane Rated 
Standards. 
 
3.4.1 
Requirements for CNG Cascade tanks 
In addition to the requirements for tanks listed in section 3.4, the following are applicable 
to CNG tanks: 
i. Each cylinder or bulk tank used for the storage of CNG shall be equipped with an 
approved pressure relief device and isolation valve which shall be capable of 
shutting off the pressure -relief device. 
ii. Piping and gas storage systems shall be protected against over-pressure by safety 
relief devices.  Relief devices installed to protect the storage systems shall be such 
that it limits the pressure to 120 per cent above the maximum allowable working 
pressure of the system or the pressure which produces a loop stress of 75% of the 
specified minimum yield strength, whichever is lower. 
iii. A shut-off valve shall not be installed between the pressure relief valve and the gas 
unit or bulk tank except that a shut-off valve may be used on multiple valve 
installations where the arrangements of the valve will provide full required flow 
through the safety relief devices at all times.  The opening or connection between 
the gas storage unit and safety relief device or devices shall have at least the 
combined areas of all connected safety relief device inlets.