GUIDELINES FOR THE ESTABLISHMENT AND OPERATIONS OF A GAS 
RETICULATION FACILITY IN NIGERIA 
Code: DPR Guide 0028 - 2020 
 
Revision Date: 1st September 2020 
 
 
 
This is a property of the Department of Petroleum Resources. All rights reserved  
 
17 
3.9 
Metering 
All meters shall be installed in such a manner as to prevent undue stresses on the 
connecting piping and/or the meter. Customers’ meters and regulators may be located 
either inside or outside of buildings, depending on local conditions.   
When located outside of buildings, meters and service regulators shall be installed in a 
location that is readily accessible and where they will be reasonably protected from 
damage and corrosion.  
3.10 Emergency Systems 
The following emergency system shall, at the minimum, be installed in the facility: 
i. 
Gas and fire detection system shall be installed and routinely tested.  
ii. 
Appropriate warning notices, safety signs and instructions, shall be positioned at 
strategic locations and control rooms.  
iii. 
Adequate intrinsically safe lighting systems of explosion-proof type shall be 
installed at points to aid safety, security and dentification of the product(s) 
(signage and labels). Note: vent outlets and potential release points shall be 
avoided. 
iv. 
Where numerous storage vessels are used, consideration should be given to 
separating these into isolatable sub-groups.  ESDs activating these isolation valves 
shall be provided both locally at each exit point from the storage site and remotely. 
 
3.11 Fire/Blast Walls 
The purpose of a firewall is to protect vessel or vessels from thermal radiation from a fire 
nearby and to ensure adequate dispersion distance to boundaries, buildings and sources 
of ignition for LPG leaking from the vessel or its fittings where normal separation distances 
cannot be achieved. The walls shall, at the minimum, be of the following features: