Applicable to all Oil & Gas Operators GUIDELINES FOR THE ESTABLISHMENT OF AN AUTOGAS REFUELLING STATIONS AND ADD-ON GAS FACILITY IN NIGERIA Code: DPR Guide 0042 - 2020 Revision Date: 1st September 2020 This is a property of the Department of Petroleum Resources. All rights reserved 14 Table 3.1 Minimum Safety Distances from LNG Storage Tank to Adjoining Properties or Amenities TANK STORAGE CAPACITY (MT) AT LNG DENSITY 450kg/m3 MINIMUM DISTANCE FROM EDGE OF IMPOUNDMENT OR LNG TANK DRAINAGE SYSTEM TO PROPERTY/AMENITIES (m) MINIMUM DISTANCE BETWEEN STORAGE TANKS (m) 0.9 - 3.4 4.6 1.5 3.4 – 28.3 7.6 1.5 28.3 – 51.3 15 1.5 51.3 – 119.3 23 1.5 > 119.3 30 Note: Bund wall installations are critical for LNG facilities 3.3.2 Separation Distances for CNG facilities Individual cylinders used for the storage or dispensing natural gas shall be located with respect to the nearest building or compressor equipment or other sources of ignition in accordance with Table 3.2. Table 3.2 Isolation distances from building and boundaries to CNG Gas storage Unit(s) Total capacity of onsite Gas storage (Cubic Ft) Minimum distance (metres) Minimum on-site distance between Gas storage units and a 4hr. FRR concrete or Masonry wall (metres) Up to 1,100 (5MT) 5 1.0 1,100 to 2,450 (5- 70MT) 7.5 1.0 Note: a. A blast wall or fire clearance zone of a minimum 3 metres shall be maintained around the perimeter fence of any CNG storage facility. b. Firewall shall be installed to adjoining residential or public buildings.