Library / GUIDE FOR THE ESTABLISHMENT AND OPERATIONS OF DOWNSTREAM GAS FACILITIES IN NIGERIA (LPG, CNG, LNG) ISSUED BY
GUIDE FOR THE ESTABLISHMENT AND OPERATIONS OF DOWNSTREAM GAS FACILITIES IN NIGERIA (LPG, CNG, LNG) ISSUED BY
Page 68 of 194
Applicable to all Oil & Gas Operators GUIDELINES FOR THE ESTABLISHMENT OF AN AUTOGAS REFUELLING STATIONS AND ADD-ON GAS FACILITY IN NIGERIA Code: DPR Guide 0042 - 2020 Revision Date: 1st September 2020 This is a property of the Department of Petroleum Resources. All rights reserved 15 3.3.3 Separation Distances for LPG. The separation distance for LPG tanks within an Autogas Refuelling and refilling are depicted in Table 3.3. The requirement for underground installations are depicted in Table 3.4. Table 3.3 Minimum Separation Distances for Above Ground LPG Storage Tanks Capacity (Metric Tonnes) Separation Distance (Meters) from tanks to the line of Adjoining Properties, Control buildings, or fixed source of ignition. Of any single tank Of any group of tanks From Adjoining Property that May be Developed/Non- Public & Non- Residential From Public and Residential Boundaries Between tanks A: No fire wall B: With Fire wall A: No fire wall B: With Fire wall 0.1 – 5 0.1– 5 5 5 30 15 1.0 5.1 - 10 5.1 - 10 7.5 5 30 20 1.0 10.1 – 60 10.1 – 60 15 7.5 50 30 1.5 60.1 - 150 60.1 – 150 22.5 11 50 30 ¼ of sum of the diameter of 2 adjacent vessels 150.1 – 300 150.1 – 300 30 15 50 30 Table 3.4: Minimum Separation Distances for Underground LPG Storage Tanks Capacity (Metric Tonnes) Separation Distance (Meters) from the relief valve to the line of Adjoining Properties, Control buildings, or fixed source of ignition. 0.1 - 10 3 >10.1 7.5
OtherPDF68