Library / GUIDE FOR THE ESTABLISHMENT AND OPERATIONS OF DOWNSTREAM GAS FACILITIES IN NIGERIA (LPG, CNG, LNG) ISSUED BY
GUIDE FOR THE ESTABLISHMENT AND OPERATIONS OF DOWNSTREAM GAS FACILITIES IN NIGERIA (LPG, CNG, LNG) ISSUED BY
Page 69 of 194
Applicable to all Oil & Gas Operators GUIDELINES FOR THE ESTABLISHMENT OF AN AUTOGAS REFUELLING STATIONS AND ADD-ON GAS FACILITY IN NIGERIA Code: DPR Guide 0042 - 2020 Revision Date: 1st September 2020 This is a property of the Department of Petroleum Resources. All rights reserved 16 The separation distances from surrounding buildings within the service station should not be less than those specified in Table 3.5 Table 3.5 Separation Distance within an LPG Refuelling and Refilling Station LPG Tank with submersible pump Extended fill connection of LPG tank LPG Dispenser Fill Connection of LPG Vehicle LPG tank with submersible pump - - 3m 3m LPG Dispenser 3m 3m - - Underground petrol tank manhole or filling point 1.5m 3m 3m 3m Petrol tank vents (in plan) 3m 3m 3m 3m Petrol/Diesel pumps/Dispensers (Flameproof) 3m 3m 1.5m 1.5m Site boundary, buildings, fixed source of ignition 7.6m 7.6m 4.25m 4.25m 3.4 Minimum Requirement for Storage Vessel/Tanks The storage tank/vessel shall be designed, constructed and installed by DPR accredited/approved company in accordance with internationally recognised standards. It shall comply with the following: i. The storage tank/vessel shall be located in a manner that allows safe access and subsequent removal if required, clear of any building foundations or underground features, such as drains and tunnels. Additionally, the Location shall not allow any