Afrindustria/ Gas Gap Monitor

Library / GUIDE FOR THE ESTABLISHMENT AND OPERATIONS OF DOWNSTREAM GAS FACILITIES IN NIGERIA (LPG, CNG, LNG) ISSUED BY

GUIDE FOR THE ESTABLISHMENT AND OPERATIONS OF DOWNSTREAM GAS FACILITIES IN NIGERIA (LPG, CNG, LNG) ISSUED BY

Page 83 of 194

Open the PDF at page 83

 
 
 
 
Applicable to all Oil & Gas Operators  
GUIDELINES FOR THE ESTABLISHMENT OF AN AUTOGAS 
REFUELLING STATIONS AND  ADD-ON GAS FACILITY IN NIGERIA 
Code: DPR Guide 0042 - 2020 
 
Revision Date: 1st September 2020 
 
 
 
This is a property of the Department of Petroleum Resources. All rights reserved  
 
30 
iii. 
At least two dry powder fire extinguishers less than 9kg each and suitable for 
appropriate Gas fires with a test fire rating of at least 21A and 183B as defined in 
MSA EN 3-7:2004 should be readily available at strategic locations to deal with 
fires adjacent to the meter/vehicle being filled. 
iv. 
During refuelling, vehicles shall be turned off.  
v. 
Vehicle routes, to and from the dispensing area shall be laid out such that there 
is no need for vehicles to pass through the fuel delivery demarcation area whilst 
delivery is taking place.  All vehicle movement routes and restrictions on the 
Refuelling Station should be clearly identified by the use of signs or arrows (i.e. 
entrance, exit etc.). 
vi. 
Warning/safety signs shall be conspicuously displayed at dispensing points. 
vii. 
Fire hydrant system and booster pumps shall be made available.  
4 
SANCTIONS 
These Guidelines provide the requirements for establishing a Autogas and Add on facilities 
in Nigeria. Noncompliance with the requirements of this Guidelines shall be deemed as 
violations to relevant sections of the Petroleum Act 1969 as amended, Petroleum  
Regulations 1967 & subsequent amendments and Mineral Oils (Safety) Regulation, 1997. 
These violations may result in applicable consequence management, including, but not 
limited to, fines, penalties and/or revocation of license. 
5 
GLOSSARY 
Abbreviations, terms and references used in this document are explained hereunder:  
AGS  
Automated Gas System   
ALARP 
As Low As Reasonably Practicable 
ATC  
Approval to Construct  
CCTV 
Closed Circuit Television