3.2.2 Procedure  
3.2.2.1 Extract a reasonable quantity of the petroleum and petroleum product sample after 
a thorough mixing into a clean glass cylinder. 
3.2.2.2 The hydrometer is then gently lowered into the sample while the thermometer is 
used to stir the sample until the temperature reading becomes steady. The temperature at 
this point is read and noted and the gravity of the sample is read from the hydrometer at 
the meniscus cut on the hydrometer stem while it is stationary and freely floating in the 
sample. The reading is then adjusted with appropriate meniscus correction applicable to 
that instrument to give the accurate SG or API Gravity of the sample to the equivalent value 
at 60/60oF using the appropriate ASTM table. 
3.2.3 Precautions 
3.2.3.1   Any air bubbles on the surface of the sample in the cylinder should be mopped up 
with clean filter paper before readings are taken. 
3.2.3.2 There should be no air current in the environment in which the test is being carried 
out. 
3.3   Procedure for Determining the Base Sediment and Water Contents (BS&W) of 
Petroleum and Petroleum Product Sample 
3.3.1 Approved Method 
3.3.1.1 The approved method for determining the BS&W of petroleum and petroleum 
product sample shall be with the use of the distillation equipment or any other method as 
approved by the Director of Petroleum Resources. The steps to follow shall generally 
conform to those outlined in ASTM D4006 and D95. In crude oil, the amount of water as 
determined by this method (D4006) shall be used to correct the volume involved in the 
custody transfer of the petroleum batch under test.  
3.3.2 Equipment Specification 
3.3.2.1 The apparatus shall be as shown in the figure in Appendix I. It shall consist of a glass 
distillation flask, a condenser, a graduated glass trap and a heater. Other types of 
distillation apparatus will be acceptable for this method provided they can be 
demonstrated to operate within the precision established with the preferred apparatus. 
3.3.3 Preparation of Test Samples 
3.3.3.1 The sample size shall be selected such that the higher the expected water content 
of the petroleum batch under test, the smaller the sample quantity. Hence sample sizes will 
be inversely proportional to the expected water cut.  As a general rule, the following 
proportional sizes shall be adopted: