49 | P a g e 1.6.3 Operation and Maintenance 1.6.3.1 Turbine meters shall be operated and maintained in accordance with the guidelines of the manufacturer and those stipulated in the appropriate reference standards. 1.6.3.2 The meter linearity is to be proved at a minimum of six points over the manufacturer’s specified range to include the minimum flow rate, the maximum flowrate and four equally spaced points between the minimum and the maximum flow rate. 1.7 Coriolis Meters 1.7.1 Description 1.7.1.1 Coriolis meters measure mass flow rate and density. A Coriolis meter consists of a sensor and a transmitter. A typical Coriolis sensor has one or two tubes through which the fluid flows. 1.7.1.2 A Coriolis meter may also be configured to indicate volumetric flow rate. The volumetric flow rate may be determined by dividing the mass flow rate by the measured density at flowing conditions. 1.7.2 Design and Selection 1.7.2.1 Coriolis meters for custody transfer meter purposes shall satisfy that its application, proving facilities can reliably and consistently meet the accuracy criteria of all parties engaged in the transaction and shall generally be carried out in accordance with API MPMS Chapter 5.6 and other relevant standards. 1.7.3 Operation and Maintenance 1.7.3.1 Coriolis meters shall be operated and maintained in accordance with the guidelines of the manufacturer and those stipulated in the appropriate reference standards. 1.7.3.2 Changes in fluid temperature as well as pressure shall be monitored and shall be compensated to minimize its influence on the accuracy the meter. 1.8 Multipath Ultrasonic Flow meters 1.8.1 Description Ultrasonic meters are inferential meters that derive the liquid flow rate by measuring the transit times of high- frequency sound pulses. They also measure flow rate using ultrasound, which can either be by “Doppler Method” or “Transit time differential method. 1.8.2 Design and Selection 1.8.2.1 Consideration shall be given to the following items in designing and selecting Ultrasonic flow meters: 1.8.2.2 The class, type of piping connections, materials and the dimensions of the equipment to be used; minimum and maximum operating flow rates; space required for the installation of the metering and proving system; acceptable pressure drop across the meter and minimum and maximum ambient and process temperatures shall generally be in accordance with API MPMS Chapter 5.8 and other relevant standards. 1.8.3 Operation 1.8.3.1 After an Ultrasonic flow meter is calibrated to determine one or more calibration coefficients, these coefficients shall be entered to the Ultrasonic flow meter Signal Processing Unit (SPU) in the presence of representative of the Department of
GuidelinesPDF50