67 | P a g e purpose of drawing up a calibration chart for the tank to show quantity of petroleum and petroleum products at any given depth. 2.5.3 Frequency of Calibration 2.5.3.1 All new tanks shall be calibrated before commissioned to service and mandatorily after every five years of its operational life. 2.5.3.2 A tank shall also be automatically due for recalibration, if the circumferential reading shows a difference of 0.015% and above, at a reference point, over the reading of the last calibration of the tank. 2.5.3.3 A tank shall be recalibrated whenever the deadwood has changed in configuration or arrangement. 2.5.3.4 A tank shall be recalibrated on relocation of the tank to another position. 2.5.3.5 A tank shall be recalibrated after any major repair or maintenance of the tank 2.5.4 Applicable Standard Calibration method shall be as outlined in latest American Petroleum Institute Manual of Petroleum Measurement Standard (API MPMS) Chapters 2.2A, 2.2B, 2.2D, 2.2F, API Standard 2555 (Method of Calibration by Liquid Calibration) as well as ISO 7507-5. 2.5.5 General Practices 2.5.5.1 Before a tank is calibrated, it shall be ascertained that the tank has been filled at least once with a liquid of a density equal to or greater than the normal service liquid. 2.5.5.2 All tanks in service shall be cleaned out and checked for bottom alignment every five years. 2.5.5.3 Any maintenance or repair job that involves replacement of plate sections or alteration of the “Deadwood” of the tank shall automatically invalidate the existing tank capacity tables and a new calibration of the tank shall be carried out before re- commissioning. 2.5.5.4 Any modification to the tank changes its capacity by more than 0.015% of the original shall invalidate the existing tank table. 2.5.5.5 There shall be no movement of petroleum or petroleum products into or out of the tank during calibration. 2.5.5.6 Before a tank shall be deemed ready for calibration, it shall be thoroughly cleaned and degassed. 2.5.6 Manual Tank Strapping 2.5.6.1 Calibration Equipment These shall be as stated in the reference standards and shall comply with appropriate specifications. The essential equipment shall be the same with those for taking measurements of tank shells above ground and shall always be maintained in good condition. Both the tape for height measurement and that for circumference measurement shall themselves have been calibrated in accordance with the Part III Section 2.4 or possess a current certificate of recent calibration at 68ᵒF (20ᵒC) in accordance with a recognized National Bureau of Standard. Also, the equipment for determining temperature and gravity shall be as follows: -
GuidelinesPDF68