81 | P a g e 1.8 Orifice Plate Installation Straight Run Requirement with Flow conditioners Minimum straight run lengths for orifice runs and other flow elements shall be in accordance with ISO 5167-2 and installation of flow conditioners as recommended in API MPMS 14.3.2/AGA report No.3 Part 2. 1.9 Inspection and Maintenance The orifice meter shall be validated at least on quarterly basis and the exercise shall be witnessed by a DPR representative. The validation exercise shall involve the following: i. Orifice plate visual inspection – measurement of the orifice bore diameter (dm), pipe inside diameter (Dm), Orifice outside diameter (D), orifice thickness and the departure from flatness. The maximum allowable departure from flatness shall be 0.005(Dm – dm) ii. Calibration of field instruments -flow transmitters, pressure transmitters, temperature sensors, Gas chromatograph, densitometers, flow computers in line with their footprint certificate iii. The physical instruments – temperature probe, resistors, voltmeters, pressure gauge, used in the calibration exercise must be tagged with details of the calibration date and due date, and the certificates must be valid and made available for sighting by the DPR representative. A HEADER DETAILS STATUS 1 Company name 2 Date of Inspection 3 Name of Inspector(s) B GENERAL INFORMATION 1 Serial number 2 Nominal Pipe diameter 3 Fluid measured (gas/liquid) 4 β ratio limit C METER TUBE 1 Type of orifice holder (flange/fitting) 2 manufacturer 3 Serial number 4 Flow conditioner (Yes/No) 5 Type of flow conditioner 6 How fastened? (welded/flanged/pinned) 7 Dimensions Length: Upstream diameter: Downstream diameter: First pipe connection: Second pipe connection: Upstream pressure tap: Downstream pressure tap: 8 Meter run type 9 Meter tube temperature
GuidelinesPDF82